Viessmann Heat Pump: Heating water piping practice and pressure limit
Heating water piping practice and pressure limit on a Viessmann heat pump: Support all piping with hangers and never let the indoor unit carry the pipe weight. Use two wrenches on fittings so the connector is not twisted. The maximum allowable working pressure is 30 psig (2 bar); exceeding it or the listed temperatures damages the unit and voids the warranty.
Applies to: Indoor unit heating water and DHW connections
How to fix heating water piping practice and pressure limit: step by step
- Flush the heating system thoroughly, especially before connecting to an existing system.
- Install isolation valves so system components can be isolated.
- Use approved pipe sealant or Teflon tape on the fittings.
- Hold the connector with one wrench and tighten the fitting with a second wrench.
- If no DHW tank is connected, cap the DHW tank supply connection.
- Keep 2 in. (50 mm) from uninsulated hot water pipes to combustible parts, unless the pipe has suitable insulation.
- Install a temperature gauge (field supplied) in the supply piping near the heat pump.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
0200280340430510780340043AM2V 020028AM2V 034043AM2V 051078
More commissioning tips for heat pump
Source: Vitocal 100-AW AM2V Technical Data Manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.