Viessmann Heat Pump: Heating water piping and connections (indoor unit)
Heating water piping and connections (indoor unit) on a Viessmann heat pump: Piping must be supported by hangers, never by the indoor unit or its components. Use isolation valves so system parts can be serviced on their own. Flush the heating system before connecting the heat pump, especially on an existing system.
Applies to: Indoor unit heating water and DHW connections
How to fix heating water piping and connections (indoor unit): step by step
- Thoroughly flush the heating system, particularly before connecting to an existing system.
- Connect the indoor unit to the heating system.
- Use approved pipe sealant or Teflon tape on the installation fittings.
- Use the two-wrench method when tightening fittings: one wrench holds the pipe, the other turns the fitting.
- Keep the heating water maximum allowable working pressure at or below 30 psig (2 bar).
- Keep at least 2 in. (50 mm) between uninsulated hot water pipes and combustible material, unless the pipe has suitable insulation (follow local rules).
- If no DHW tank is connected, close the DHW tank supply connection with a cap.
- Install a field-supplied temperature gauge in the supply piping near the heat pump.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
0200280340430510780340043AM2V 020028AM2V 034043AM2V 051078
Source: Vitocal 100-AW AM2V Technical Data Manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.