Viessmann Heat Pump: Freeze protection tab
Freeze protection tab on a Viessmann heat pump: The ANTIFREEZE tab sets the freeze set point. Breaking it off is permanent and is only allowed on closed loops that have adequate antifreeze.
Applies to: Liquid to refrigerant heat exchanger
How to fix freeze protection tab: step by step
- On closed loops with adequate antifreeze, break off the ANTIFREEZE tab with needle nose pliers if a 20°F (-7°C) set point is wanted.
- On open loops, leave the tab in place to keep the 38°F (3°C) set point.
- Do not remove the tab on open loops or on closed loops with minimal freeze protection, as this voids the warranty.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
More commissioning tips for heat pump
Source: Vitocal 100-WA installation, service and operating instructions, p. 45. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.