Viessmann Heat Pump: DHW desuperheater piping requirements
DHW desuperheater piping requirements on a Viessmann heat pump: Use isolation valves and two drain valves so the pump can be serviced without draining the tank. Use a horizontal swing check valve to stop the tank overheating. Copper must match the unit fittings; if 1 in. (25 mm) copper is used, reduce it as close to the tank as possible. Use metal fittings within 12 in. (300 mm) of the desuperheater tee. With a Marathon plastic tank use mechanical fittings at the tank only, and never use plastic fittings between the tank and the unit. Follow the tank installation instructions.
Applies to: DHW tank with desuperheater
How to fix dhw desuperheater piping requirements: step by step
- Install isolation valves and two drain valves (tank draining and purging).
- Install a horizontal swing check valve.
- Use metal fittings within 12 in. (300 mm) of the desuperheater tee.
- Reduce 1 in. copper to match the unit as close to the tank as possible.
- Upsize long pipe runs if pressure drop is too high.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
More commissioning tips for heat pump
Source: Vitocal 100-WA technical data manual, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.