Viessmann Heat Pump: Decommissioning and refrigerant recovery
Decommissioning and refrigerant recovery on a Viessmann heat pump: Recovery and decommissioning need a technician familiar with the equipment. Take a refrigerant and oil sample first if reuse may be needed.
Applies to: Vitocal 100-AW AM2V
How to fix decommissioning and refrigerant recovery: step by step
- Confirm electrical power is available, then isolate the system electrically.
- Take oil and refrigerant samples before starting, if analysis may be needed.
- Pump the system down if possible. If not, fit a manifold to recover from several points.
- Use recovery equipment and cylinders approved for flammable refrigerant, with calibrated scales.
- Put the cylinder on the scales before recovery starts.
- Do not fill cylinders above 80% of volume with liquid.
- Do not exceed the cylinder's maximum working pressure, even briefly.
- Remove full cylinders and equipment from site promptly and close all isolation valves.
- Do not mix refrigerants in recovery units or cylinders.
- Do not charge recovered refrigerant into another system unless it has been cleaned and checked.
- Label the equipment as decommissioned and emptied, with date and signature. Add a flammable refrigerant label if applicable.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
0200280340430510780340043AM2V 020028AM2V 034043AM2V 051078
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 11. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.