Viessmann Heat Pump: Condensate drain and p-trap
Condensate drain and p-trap on a Viessmann heat pump: The unit has an integrated p-trap. A vent is only needed where a double p-trap can form.
Applies to: All Vitocal 100-WA units
Common causes of condensate drain and p-trap
- Unlevel drain piping that lets standing water form a second p-trap, causing an air lock and no drainage
How to fix condensate drain and p-trap: step by step
- Provide a condensate drain connection; add a condensate pump if needed.
- Install a vent only downstream of the unit p-trap, and only if a double p-trap condition is possible.
- Never place a vent between the unit and its p-trap.
- Install extra tees near the unit for drain cleaner access and cap or plug all extra openings.
- Never tie the condensate drain into the discharge line of a well water system.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.