Viessmann Heat Pump: Closed loop water quality and antifreeze limits
Closed loop water quality and antifreeze limits on a Viessmann heat pump: Treat feed water where mineral content or hardness is high. Keep total hardness of fill and top-up water under 350 ppm and avoid sulphur-containing feed water. Check pH after running; it should be 7 to 9. Use only antifreeze made for water source heat pumps, never automotive silicate antifreeze. Keep antifreeze at or below 35%; above that performance drops. Provide the owner with the SDS for the antifreeze used.
Applies to: Closed loop systems
Common causes of closed loop water quality and antifreeze limits
- Hardness above 350 ppm
- pH outside 7 to 9
- Silicate-based automotive antifreeze
- Antifreeze above 35%
How to fix closed loop water quality and antifreeze limits: step by step
- Test fill water for hardness and sulphur; treat if needed.
- Check pH after operation; correct it if outside 7-9.
- Use only heat pump rated antifreeze.
- Keep glycol at or below 35%.
- Give the owner the antifreeze SDS and note the system is glycol filled.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
Source: Vitocal 100-WA technical data manual, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.