Viessmann Heat Pump: Closed loop purging and pump mounting
Closed loop purging and pump mounting on a Viessmann heat pump: Air trapped in the pump will burn it out quickly. Purging needs a minimum velocity in every branch. With several heat pumps on one loop, only one auto purge kit is used.
Applies to: Closed loop systems
How to fix closed loop purging and pump mounting: step by step
- Mount the ground loop pump vertically so air cannot be trapped in it.
- Achieve at least 2 ft/s in every branch of the ground loop while purging.
- Use the purge ports for anti-freeze charging.
- With two or more heat pumps on one loop, install only one auto purge kit, ideally on the highest unit.
- Install check valves and a Y-strainer on each unit.
- Keep the auto purge tank ½ to ¾ full at all times.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
More commissioning tips for heat pump
Source: Vitocal 100-WA installation, service and operating instructions, p. 40-41. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.