Updated · by Aurora Star Tech Inc.

Closed loop purging and pump mounting on a Viessmann heat pump: Air trapped in the pump will burn it out quickly. Purging needs a minimum velocity in every branch. With several heat pumps on one loop, only one auto purge kit is used.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Closed loop systems

How to fix closed loop purging and pump mounting: step by step

  1. Mount the ground loop pump vertically so air cannot be trapped in it.
  2. Achieve at least 2 ft/s in every branch of the ground loop while purging.
  3. Use the purge ports for anti-freeze charging.
  4. With two or more heat pumps on one loop, install only one auto purge kit, ideally on the highest unit.
  5. Install check valves and a Y-strainer on each unit.
  6. Keep the auto purge tank ½ to ¾ full at all times.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Heat Pump codes

Models

AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056

More commissioning tips for heat pump

Source: Vitocal 100-WA installation, service and operating instructions, p. 40-41. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.