Updated · by Aurora Star Tech Inc.

A2L refrigerant leak mitigation check on a Viessmann heat pump: On a detected leak the compressor stops, the blower runs in continuous fan mode and the display shows GAS. Use this check to confirm the mitigation is working.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocal 100-WA with R-454B refrigerant

Common causes of a2l refrigerant leak mitigation check

  • A2L refrigerant leak detected

How to fix a2l refrigerant leak mitigation check: step by step

  1. Confirm GAS fault on the information display.
  2. Via terminal interface screen 1: LFL% should be above 15%, compressor percentage 0, fan above 10%.
  3. At the control board, confirm C1 and C2 are not sending 24VAC to the compressor start relay.
  4. At the start relay, confirm the coil is not energised and the 230V load side is not energised.
  5. At the compressor plug, confirm no amp draw on common, start or run wires.
  6. At the control board ECM terminal, confirm about 12VDC between G and C.
  7. At the blower high voltage connector, confirm amp draw on T1 and T2.
  8. Do not unplug the blower motor while it is running.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Heat Pump codes

Models

AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056

Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 48. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.