Viessmann Boiler: Wiring and mounting the wall mount base and remote control
Wiring and mounting the wall mount base and remote control on a Viessmann boiler: Use 2-wire cable, AWG 18 copper. Strip the cable and pull it through the bushing into the wall mount base, then mount the base on an even wall. Watch the cable path while drilling. Connect the two wires to terminals 1 and 2 on the base, and plug the connector into socket 145 on the control unit or on the KM-BUS Expansion Module. Insert the remote control at 90 degrees into the base slot and fold it down until it snaps in. To open it, unlock it from the base with a small screwdriver. Power to the boiler, heating system and external controls must be off during the work.
Applies to: Vitotrol 200 remote control
How to fix wiring and mounting the wall mount base and remote control: step by step
- Turn off main power to the equipment, heating system and external controls.
- Strip the 2-wire cable (AWG 18 copper) and pull it through the bushing into the wall mount base.
- Mount the wall mount base on an even wall, watching the cable path when drilling.
- Connect the wires to terminals 1 and 2 on the base and plug the connector into socket 145 on the control unit or KM-BUS Expansion Module.
- Insert the remote control at 90 degrees into the base slot, press the top of the housing to seat it, then fold down and snap it in.
- To remove, unlock the remote control from the base with a small screwdriver.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotrol 200 installation instructions, p. 2, p. 5. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.