Viessmann Boiler: Underfloor heating limit aquastat and electronic limits
Underfloor heating limit aquastat and electronic limits on a Viessmann boiler: The control's electronic high limit does not replace a separate limit aquastat required for underfloor heating. The aquastat switches the heating circuit pump off when supply temperature exceeds its set value. Supply temperature then cools slowly, so automatic reset can take several hours. Electronic limits are set with coding C6 (high) and C5 (low), both with a range of 34 to 262 F / 1 to 127 C.
Applies to: Underfloor heating
How to fix underfloor heating limit aquastat and electronic limits: step by step
- Install a limit aquastat for underfloor heating systems.
- Set the electronic max limit with coding C6 and the min limit with coding C5.
- Allow several hours for automatic reset after the aquastat trips.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B
Source: Vitotronic 200 KW2 service instructions, p. 49. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.