System version 5: heating circuit with one low temperature circuit on a Viessmann boiler: Vitocrossal 300 controlled by a Viessmann boiler control with outdoor reset, modulating boiler water temperature and load-dependent sequential control of two-stage or modulating burners. The Vitocrossal 300 has two return connections; higher return temperature circuits go to the upper connection and lower return temperature circuits go to the lower connection. The LON-BUS sets the boiler supply temperature from the highest mixing valve circuit temperature plus an adjustable differential.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: System version 5, Vitocrossal 300

How to fix system version 5: heating circuit with one low temperature circuit: step by step

  1. Connect at least 15% of the rated output to the lower return connection.
  2. Code every Vitotronic 100 GC1 as shown in the system version 5 coding table.
  3. Check the connection diagram on site for completeness and function, because it is only a recommendation.
  4. Wire single-phase and three-phase pumps through field-supplied motor contactors or starters.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitotronic 100, type GC1

Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 18-20. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.