Viessmann Boiler: Reversing the mixing valve motor rotation
Reversing the mixing valve motor rotation on a Viessmann boiler: Used when the mixing valve must turn the other way for the installation. The motor plug is turned 180° to reverse rotation.
Applies to: Mixing valve motor
How to fix reversing the mixing valve motor rotation: step by step
- Remove the cover of the mixing valve motor.
- Pull out the 3-pole plug A and reinsert it turned 180°.
- Run the relay test on the control unit and confirm the valve moves to Open and Closed as expected.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
Source: Vitotronic 200-H installation and service instructions, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.