Viessmann Boiler: Replacing the printed circuit board (cascade electronics)
Replacing the printed circuit board (cascade electronics) on a Viessmann boiler: Replacement of the cascade electronics printed circuit board. Record and restore settings.
Applies to: Vitotronic 300-K MW1S cascade electronics module A2
How to fix replacing the printed circuit board (cascade electronics): step by step
- Record all coding and adjustments made at the control unit.
- Replace the printed circuit board.
- Set coding 8A to 176.
- Set coding address 92 to 92:160.
- Re-enter the recorded coding and adjustments.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300-K MW1S installation and service instructions, p. 119. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.