Viessmann Boiler: Replace main PCB

Updated · by Aurora Star Tech Inc.

Replace main PCB on a Viessmann boiler: Keep the current settings before swapping the main PCB, then restore the required codings.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Main PCB of Vitotronic 200-H

How to fix replace main pcb: step by step

  1. Record all codings and adjustments made at the control unit.
  2. Replace the PCB.
  3. Set coding 8A to 176.
  4. Set coding 92 to 180.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300

Source: Vitotronic 200-H HK1M installation and service instructions, p. 34. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.