Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Boiler: Quick heat-up and quick setback for mixing valve circuits

Updated · by Aurora Star Tech Inc.

Quick heat-up and quick setback for mixing valve circuits on a Viessmann boiler: Room temperature influence can be boosted briefly. It acts only when the set room temperature changes by at least 2 °C / 3.6 °F.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Mixing valve circuits with room temperature input

How to fix quick heat-up and quick setback for mixing valve circuits: step by step

  1. Quick heat-up: press the party button, or switch from reduced to normal heating, to raise the room set point by 2 °C / 3.6 °F or more.
  2. Quick setback: press the economy button, or switch from normal to reduced heating, to lower the room set point by 2 °C / 3.6 °F or more.
  3. Quick heat-up and setback stop when the set room temperature is reached.
  4. Use coding b6 for quick heat-up/setback and b2 for room temperature influence.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

More settings shortcuts tips for boiler

Source: Vitotronic 300-K MW1S installation and service instructions, p. 114. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977