Viessmann Boiler: LON extension with on-site cable and junction boxes
LON extension with on-site cable and junction boxes on a Viessmann boiler: For extensions up to 900 m / 3000 ft using on-site cable. Up to 99 participants are allowed.
Applies to: Vitotronic 300-K MW1S LON system
How to fix lon extension with on-site cable and junction boxes: step by step
- Use Viessmann LON cable part no. 7143 495 between control units and junction boxes.
- Connect the on-site cable between junction boxes for runs up to 900 m / 3000 ft in total.
- Keep the number of participants, junction boxes and cables within the 99-participant limit.
- Confirm the cable meets the FTT-10A interface requirements (see www.echelon.com).
- Keep the two wires and shielding on every segment.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 69. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.