Viessmann Boiler: Fixed high limit has tripped (lockout)
Fixed high limit has tripped (lockout) on a Viessmann boiler: The fixed high limit shuts the boiler down with lockout when the water temperature reaches its limit. It is reset manually. It also locks out on a capillary leak or when ambient is below -10 °C / 14 °F.
Applies to: Fixed high limit on Vitotronic 100 GC1
Common causes of fixed high limit has tripped (lockout)
- Boiler water reached the fixed high limit setting
- Capillary leak
- Ambient temperature below -10 °C / 14 °F
How to fix fixed high limit has tripped (lockout): step by step
- Check the boiler water temperature and the limit setting.
- Check the capillary and the ambient temperature at the limit.
- Test the limit with its test button.
- Reset the fixed high limit manually once the cause is cleared.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 and 300-K MW1S installation and service instructions, p. 121. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.