Viessmann Boiler: External contacts A, B and C on A2
External contacts A, B and C on A2 on a Viessmann boiler: Dry contacts on A2 for heating program change, external disable and external heat demand. Heating circuit allocation uses coding addresses 91, 9A, 99 and 9b.
Applies to: Vitotronic 300-K MW1S external dry contacts
How to fix external contacts a, b and c on a2: step by step
- Wire the external contacts on A2 per the overview on pages 58 and 59 and the control panel wiring diagram.
- Contact A: closing it changes the heating program or opens the mixing valves. Allocate heating circuits with coding addresses 91 and 9A.
- Contact B: closing it shuts the burner down or closes the mixing valve. Allocated boiler or shunt pumps switch off and isolation valves close. Allocate with coding address 99.
- Contact B overrides contact A: closed mixing valve has priority over open mixing valve.
- Contact C: closing it starts the burners as needed to reach the set point at coding address 9b. Supply temperature is limited by the set minimum and maximum supply temperatures.
- Note that heating circuits are not frost protected while the mixing valve is closed, and the minimum boiler return temperature is not maintained during external disabling.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 66. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.