Viessmann Boiler: Example: outdoor temperature raises the reduced room set-point (F8:-5, F9:-14)
Example: outdoor temperature raises the reduced room set-point (F8:-5, F9:-14) on a Viessmann boiler: With an outdoor sensor, the reduced room set-point rises as outdoor temperature falls. Example: reduced room set-point 3°C / 37°F, normal room set-point 20°C / 68°F. The raise starts below -5°C / 23°F (F8) and reaches normal room temperature at -14°C / 7°F (F9).
Applies to: Vitotronic 200-H, Model HK1M
How to fix example: outdoor temperature raises the reduced room set-point (f8:-5, f9:-14): step by step
- Check that F8 is -5 and F9 is -14 (factory defaults).
- Confirm the reduced set-point (3°C / 37°F) and normal set-point (20°C / 68°F) are as expected.
- Watch the room set-point climb along the heating curve between the two outdoor limits.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
Source: Vitotronic 200-H installation and service instructions, p. 50. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.