Viessmann Boiler: Connect combustion air device adaptor (single boiler)
Connect combustion air device adaptor (single boiler) on a Viessmann boiler: Wire a combustion air blower to the Vitotronic through the adaptor board in the connection enclosure.
Applies to: Single boiler with combustion air blower
How to fix connect combustion air device adaptor (single boiler): step by step
- Disconnect power to the control and burners.
- Mount the combustion air device adaptor (PN 7134 563) on the DIN rail inside the connection enclosure, following the adaptor manual.
- Remove the jumper between terminals 16 and 17.
- Connect wire BK2 to terminal 16 and BK3 to terminal 17. Do not reverse them.
- Wire the blower motor, the normally open proving switch (120 VAC rated) and the 120 VAC supply as shown in the diagram.
- Provide disconnect means and overcurrent protection as local codes require.
- Confirm the blower is suitable for this application (see ratings table).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 / 300-K MW1S installation, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.