Viessmann Boiler: Clear the Service message after maintenance
Clear the Service message after maintenance on a Viessmann boiler: Used when the Service display and red fault indicator flash because a service limit was reached. Coding address 24 holds the service timer and must be reset after the work is done.
Applies to: Vitotronic 200 KW2
Common causes of clear the service message after maintenance
- Service limit set by coding addresses 1F, 21 or 23 has been reached
How to fix clear the service message after maintenance: step by step
- If service is done before Service is shown, set coding address 24:1 and then 24:0 to reset the service hours and interval to 0.
- Press the scan button to start the service scan.
- Scan through the service messages with the arrow buttons if more than one is stored.
- Confirm 'Acknowledge: Yes' to turn off the Service display. The red fault indicator keeps flashing.
- Press the scan button again to end the service scan.
- After maintenance, set coding address 24 back to 24:0. The red fault indicator then goes off.
- If 24 is not reset, the Service display returns at 07:00 on Monday.
- Reset burner operating hours, burner starts and fuel consumption as shown in the operating status section.
- Reset the maximum flue gas temperature to the current value using the held button combination (about 4 seconds), then confirm.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B
Source: Vitotronic 200 Service Instructions, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.