Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Boiler: Clear the Service message after maintenance

Updated · by Aurora Star Tech Inc.

Clear the Service message after maintenance on a Viessmann boiler: Used when the Service display and red fault indicator flash because a service limit was reached. Coding address 24 holds the service timer and must be reset after the work is done.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotronic 200 KW2

Common causes of clear the service message after maintenance

  • Service limit set by coding addresses 1F, 21 or 23 has been reached

How to fix clear the service message after maintenance: step by step

  1. If service is done before Service is shown, set coding address 24:1 and then 24:0 to reset the service hours and interval to 0.
  2. Press the scan button to start the service scan.
  3. Scan through the service messages with the arrow buttons if more than one is stored.
  4. Confirm 'Acknowledge: Yes' to turn off the Service display. The red fault indicator keeps flashing.
  5. Press the scan button again to end the service scan.
  6. After maintenance, set coding address 24 back to 24:0. The red fault indicator then goes off.
  7. If 24 is not reset, the Service display returns at 07:00 on Monday.
  8. Reset burner operating hours, burner starts and fuel consumption as shown in the operating status section.
  9. Reset the maximum flue gas temperature to the current value using the held button combination (about 4 seconds), then confirm.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B

Source: Vitotronic 200 Service Instructions, p. 32. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977