Viessmann Boiler: Check the supply temperature sensor
Check the supply temperature sensor on a Viessmann boiler: Use this to check a strap-on or immersion supply temperature sensor against the actual temperature.
Applies to: Supply temperature sensor, strap-on or immersion
How to fix check the supply temperature sensor: step by step
- Disconnect the sensor from the terminals.
- Measure the sensor resistance at terminal 2 of the plug.
- Compare the reading with the resistance table for the current supply temperature.
- If the value differs significantly, check the installation and replace the sensor if needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 100/300-K installation and service instructions, p. 62. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.