Viessmann Boiler: Check the room temperature sensor
Check the room temperature sensor on a Viessmann boiler: Use this check when the room temperature shown on the display seems wrong and the remote Vitotrol cannot be used.
Applies to: Room temperature sensor part no. 7408 012
Common causes of check the room temperature sensor
- Sensor reading differs clearly from the actual room temperature
- Wiring or installation position is causing a wrong reading
How to fix check the room temperature sensor: step by step
- Disconnect the wires from the sensor.
- Measure the sensor resistance at terminals 9 and 13b.
- Compare the resistance with the table for the actual room temperature.
- Compare the reading with the room temperature shown on the display (see scan page 91).
- Check the installation and replace the sensor if the deviation is severe.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300-K MW1S installation and service instructions, p. 136. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.