Viessmann Boiler: Check the fixed high limit (STB)
Check the fixed high limit (STB) on a Viessmann boiler: Test of the fixed high limit on the Vitotronic 100. The adjustable high limit is bypassed during the test.
Applies to: Vitotronic 100 GC1 fixed high limit test
How to fix check the fixed high limit (stb): step by step
- Hold down the test button (TÜV) for the test.
- Make sure a minimum flow is present. Minimum boiler flow should be 10% of the boiler flow at rated output.
- Reduce the heat consumption as far as possible. The adjustable high limit R is bypassed.
- Let the burner run until the boiler water reaches the safety temperature and the fixed high limit (STB) switches off.
- Release the test button (TÜV). The display shows fault D4.
- Wait until the boiler water is 15 to 20 °C (25 to 35 °F) below the set safety temperature.
- Press button E to reset the fixed high limit. Fault D4 clears.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Viessmann Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 72. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.