Viessmann Boiler: Check room temperature sensor
Check room temperature sensor on a Viessmann boiler: Test the separate room temperature sensor used when the remote control cannot be mounted in a suitable place.
Applies to: Room temperature sensor Part No. 7133 379
Common causes of check room temperature sensor
- Displayed room temperature differs significantly from actual room temperature
How to fix check room temperature sensor: step by step
- Disconnect the wires at the sensor terminals.
- Measure resistance at terminals 9 and 13b.
- Compare with the resistance table.
- Compare with the displayed room temperature (see page 25).
- If the difference is significant, check installation and replace the sensor if needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
Source: Vitotronic 200-H HK1M installation and service instructions, p. 39. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.