Viessmann Boiler: Carry out a LON participant check
Carry out a LON participant check on a Viessmann boiler: The participant check tests communication between the fault manager and the devices connected to it.
Applies to: Vitotronic 300-K, MW1S
Common causes of carry out a lon participant check
- Communication not established between the two devices
How to fix carry out a lon participant check: step by step
- Confirm the control is coded as fault manager (coding 79 : 1).
- Confirm the LON participant number is coded in all control units.
- Confirm the fault manager participant list is current.
- Press the two buttons together for about 2 seconds to open the participant check.
- Select the participant with the arrow buttons.
- Start the check. The display and button lights of that participant flash for about 60 seconds.
- If Check not OK appears, check the LON connection and coding.
- Repeat for other participants, then press the two buttons together for about 1 second to exit.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitotronic 100/300-K installation and service manual, p. 76. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.