Viessmann Boiler: Burner not running and boiler cold (no fault shown on display)
Burner not running and boiler cold (no fault shown on display) on a Viessmann boiler: Fault behaviour with no code on the programming unit. Work through the cases by what the display and pumps are doing.
Applies to: Vitotronic 200 KW2 burner start
Common causes of burner not running and boiler cold (no fault shown on display)
- No power to the Power Pump Module
- Low water cut-off device open (if installed)
- Faulty interconnection between Vitotronic and Power Pump Module
- Blown fuse F1 in the Vitotronic
- Pump fuses F1 to F4 in the Power Pump Module
- Open fixed high limit or other safety high limit
- Faulty burner connection cable or burner equipment (fuses, ignition module, venting equipment, motor-controlled flue damper)
How to fix burner not running and boiler cold (no fault shown on display): step by step
- Turn the emissions test switch to the position shown in the manual.
- If the programming unit display is blank: check power to the Power Pump Module, check the low water cut-off (if fitted), check the interconnection between Vitotronic and Power Pump Module, and check and replace fuse F1 in the Vitotronic if needed.
- If the display is on but no pumps run: check the interconnection to the Power Pump Module and check fuses F1 to F4 in the module. Replace the fuse and pump if needed.
- If the display is on and pumps run: measure voltage between L1 and N at the burner connector. If there is none, check the connector, burner connection cable and fixed high limit, and any other safety high limits (low water cut-off, pressure gauge).
- If voltage is present at L1 and N: measure voltage at the burner terminal with the connector connected. If there is none, check the equipment on the burner (fuses, ignition module, venting equipment).
- If voltage is present at the burner terminal: press the TUV TEST button. The burner should start after a delay (for example oil preheat). If it still does not run, repeat the checks.
- Check any defective additional equipment that could block burner start, such as a motor-controlled flue gas damper.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B
Source: Viessmann Vitotronic 200 service instructions, p. 41. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.