Viessmann Boiler: Burner motor power supply, 240 VAC 1-phase in conduit
Burner motor power supply, 240 VAC 1-phase in conduit on a Viessmann boiler: Power the burner motor from 240 VAC single phase using the factory-supplied cable and conduit.
Applies to: Burners with 240 VAC, 1PH supply and connection in conduit
How to fix burner motor power supply, 240 vac 1-phase in conduit: step by step
- Disconnect power to the burner and the boiler control.
- Connect 240 VAC to terminals 21, 22 and 23 on the DIN rail in the connection enclosure. Fit a fuseable disconnect according to local codes.
- Connect the supplied power cable to the motor terminals on the burner.
- Plug the cable plug into the socket on the DIN rail in the connection enclosure.
- Check fuse and wire gauge sizing in the burner manual.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 51. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.