Updated · by Aurora Star Tech Inc.

Boiler hot but heating circuit pumps not running on a Viessmann boiler: Check whether the pump is being called on, then check voltage and fuses.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotronic 200 KW2 heating circuit pumps

Common causes of boiler hot but heating circuit pumps not running

  • Pump not activated by control logic
  • Faulty pump connection or pump
  • Additional control such as a high limit aquastat blocking the pump
  • Blown fuse F2 in the Vitotronic
  • Blown fuses F1 to F4 in the Power Pump Module
  • Defective mixing valve motor or pump connector

How to fix boiler hot but heating circuit pumps not running: step by step

  1. Turn the emissions test switch to the position shown in the manual so the pumps run.
  2. If the pumps run: the pump is not being called. Check heating curves, desired values, heating circuit pump logic, external equipment (such as Switching Module-V) and high domestic hot water demand.
  3. If the pumps do not run: measure voltage between L and N on the connector in the Power Pump Module.
  4. If voltage is present: check the pump connection and the pump, then check any added control equipment such as a high limit aquastat.
  5. If voltage is not present: check fuse F2 in the Vitotronic and fuses F1 to F4 in the Power Pump Module.
  6. If a fuse is defective: disconnect all pump and mixing valve motor connectors, replace the fuse, then reconnect one unit at a time to find the defective unit.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B

Source: Viessmann Vitotronic 200 service instructions, p. 43. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977