Other: Mini-Split tips (part 6 of 8)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on other for mini-split. Check each one against the manual for your exact model before acting.

Control features and fan speed options

Viessmann · DLFSCBH and DLFLCBH

Microprocessor control holds room temperature, selects the best fan speed and runs self diagnostics. The fan speed can be set to high, medium, low or automatic. Automatic heating to cooling changeover applies in heat pump mode, with a deadband to prevent rapid mode cycling. Other functions include automatic restart after power failure, a 24 hour timer, indoor coil freeze protection, indoor coil high temperature protection in heat pump mode, dehumidification, fan only operation and wireless set point control.

Control system and sensors

Viessmann · Heat pump cassette systems

Thermistors in the indoor air inlet and indoor coil feed the indoor board. Heat pumps add an outdoor coil thermistor.

  1. Check the indoor air inlet thermistor and indoor coil thermistor when checking control readings.
  2. On heat pumps, also check the outdoor coil thermistor.
  3. Outdoor units also run their own microprocessor.

Controller behavior after power failure

Viessmann · DLFSDAH and DLFLDAH indoor ducted fan coils

The unit includes automatic restart. After a power failure it returns to the same operating conditions it was running at the time of failure.

Controller temperature display and automatic airflow limits

Viessmann · Ducted indoor units

The wired controller can show °F or °C and changes temperature in 1 degree steps. Do not use automatic airflow with booster fans, an outdoor air processing unit or a duct HRV.

  1. Set the display to °F or °C on the wired controller as needed.
  2. Do not run AF with booster fans, outdoor air processing units or duct HRVs; use manual SP settings instead.
  3. If the ductwork or static pressure changes, redo the SP or AF setup.

Crankcase and base pan heaters

Viessmann · All DLCURAH outdoor units

Crankcase heater is standard on all sizes; its clamps must be placed around the compressor oil sump. Base pan heater is standard on all sizes. The base pan has multiple drain holes for defrost drainage; seal them with rubber plugs only where the condensate drain must be redirected.

  1. Place the crankcase heater clamps around the compressor oil sump.
  2. If the condensate must be redirected, seal the base pan drain holes with the rubber plugs listed for the model.

Discharge capacitors before servicing the outdoor PCB

Viessmann · DLCSRB outdoor units

Electrolytic capacitors keep a charge after power is removed. Discharge them before touching the outdoor board. The manual gives the discharge resistor value as 100 ohm, 40 W (the ohm symbol is missing in the printed text).

  1. Shut off power and lock out the disconnect.
  2. Connect a discharge resistor (about 100 ohm, 40 W) or a soldering iron plug across the + and - terminals of the electrolytic capacitor. On some units the terminals are on the back side of the outdoor PCB.
  3. Confirm the capacitor is discharged before handling the board.

Discharge the inverter capacitors before service

Viessmann · DLCM(R/H)B multi-zone outdoor units with DLFSHBH high wall indoor units (Midea, Carrier, Viessmann)

The big electrolytic capacitors on the outdoor board stay charged after power-off.

  1. Turn power off and lock out.
  2. Put a resistor of about 100 ohm 40 W (or a soldering iron plug) across the + and - capacitor terminals before touching the board.

Display indicators on the indoor unit

Viessmann · DLFSHC indoor unit display

The display window shows temperature, operating feature and error codes. Some indicators light for 3 seconds when a feature is turned on or off, such as ECO, defrost, timer, Active Clean, self clean, or 46°F (8°C) heating mode.

  1. Read the display window for temperature, feature and error information.
  2. Note which feature indicator lights for 3 seconds when a mode is changed.

Do not release refrigerant before evacuation

Viessmann · All sizes

Evacuation instructions are in the outdoor unit manual. Keep the outdoor refrigerant charge until evacuation is finished.

  1. Follow the outdoor unit installation instructions for system evacuation.
  2. Do not release the refrigerant charge from the outdoor unit until evacuation is complete.

Do not use automatic airflow adjustment in these cases

Viessmann · Ducted indoor units

Automatic airflow adjustment should be avoided when the duct system has added equipment or changed.

  1. Do not adjust dampers while automatic airflow adjustment is running.
  2. Do not run automatic airflow adjustment from the remote when booster fans, an outdoor air processing unit or an HRV via duct are fitted.
  3. If the ventilation paths have changed, repeat the adjustment from step 3 of the airflow procedure.

Do not use oxygen-containing gas for leak testing

Viessmann · Leak testing and system pressurising

Never use air or gases containing oxygen for leak testing or for running refrigerant compressors. Mixtures can explode.

Do not use oxygen-containing gases for leak testing

Viessmann · All DLFSFBH units

Air or other gases containing oxygen must not be used for leak testing or running refrigerant compressors. Mixtures with oxygen can explode.

  1. Use dry nitrogen or an approved gas for pressure and leak testing.
  2. Never run the compressor with air or oxygen-containing gas.

DRYING mode behaviour and low room temperature protection

Viessmann · DRYING mode

Indoor fan is fixed at breeze and cannot be changed. In DRYING mode the compressor stops if room temperature is below 50°F (10°C) and restarts only after the room exceeds 53.6°F (12°C).

Electrical shock hazard before service

Viessmann · All DLFSFBH units

Power to the unit must be off before installing, modifying or servicing it.

  1. Turn the main electrical disconnect to OFF. There may be more than one disconnect.
  2. Lock out and tag each disconnect with a warning label.

Energy saving recommendations

Viessmann · All models

Owner guidance to improve efficiency.

  1. Pick a comfortable set point and avoid constant changes.
  2. Keep the filter clean.
  3. Use drapes or shades on very hot days.
  4. Limit run time with the TIMER function.

FAN mode operation

Viessmann · DLFSFBH 12K

In FAN mode the outdoor fan and compressor are off. Temperature setting is disabled.

  1. Select high, medium, low or auto indoor fan speed.
  2. Louver operates the same as in COOLING mode.
  3. Auto fan control is available in this mode.

Field wiring between indoor and outdoor unit

Viessmann · DLFSFBH 12K ductless system field wiring

Power and communication run as four conductors. Two are line voltage, one is the communication (S) wire, and one is ground. The polarity matters. Do not use BX cable.

  1. Use 14/3 stranded wire with ground, rated 600 V, for the outdoor-to-indoor run.
  2. If there is high EMF interference and communication problems, you may use 14/2 stranded shielded wire in place of L2 and S. Land the shield to ground at the outdoor unit only.
  3. Size wire per NEC/CEC and local code, using the outdoor unit MCA and MOCP values.
  4. Make every connection firmly. Keep wires away from refrigerant tubing, the compressor and moving parts.
  5. Provide a disconnect within sight of and readily accessible from the unit.

Final tubing check before charge

Viessmann · Factory tubing on indoor and outdoor units

Check that the factory tubing on both indoor and outdoor units has not shifted in shipping.

  1. Make sure tubes do not rub against each other or sheet metal.
  2. Check the wire ties on the feeder tubes are secure and tight.

Final tubing check before charging

Viessmann · Refrigerant circuit

Factory tubing can shift in shipping and cause rubbing and vibration.

  1. Check that factory tubing on the indoor and outdoor units has not moved.
  2. Make sure no tubes rub against each other or against sheet metal.
  3. Check that feeder tube wire ties are secure and tight.
  4. Never use the system compressor as a vacuum pump.

FOLLOW ME function

Viessmann · FOLLOW ME

Pressing FOLLOW ME on the remote or wired controller makes the buzzer sound and the PCB uses the remote's room temperature, shielding the unit's own room sensor. Repeated remote signals every 3 minutes do not beep. If no remote signal for 7 minutes, or FOLLOW ME is pressed again, it turns off and the unit uses its own room sensor.

FORCED COOLING and FORCED AUTO modes

Viessmann · Forced operation

FORCED COOLING: compressor runs at F2 frequency and indoor fan runs BREEZE; after 30 minutes the unit enters AUTO at 75.2°F (24°C). FORCED AUTO is normal AUTO with a 75.2°F (24°C) setpoint.

Heating performance in cold weather

Viessmann · Vitocal IND-F floor console, Size 12 (12XAK)

The HEAT function performance drops as outdoor temperature falls.

  1. In very cold outdoor conditions, use this unit together with other heating appliances.

How to read the cooling capacity tables

Viessmann · D5CSRA cooling performance tables

Each cooling table is set up by airflow (CFM), outdoor dry bulb and indoor wet bulb. Find the block for your airflow and outdoor temperature, then read the column for your indoor dry bulb. TC is total cooling capacity in Btu/h, S/T is sensible-to-total ratio, and PI is power input in kW. Only highlighted values are tested; the rest are simulated for reference.

  1. Pick the table for your indoor unit type and capacity (Tables 14 to 71).
  2. Select the airflow block that matches the fan speed.
  3. Find the outdoor dry bulb row for the actual outdoor temperature.
  4. Match the indoor wet bulb column and the indoor dry bulb sub-column.
  5. Read TC, S/T and PI from that cell and use highlighted values as tested data.

How to read the D5CSRA cooling performance grids

Viessmann · D5CSRA cooling performance tables, Tables 14 to 42 (pages 13 to 130)

Each grid gives total cooling (TC), sensible/total ratio (S/T) and power input (PI) for one capacity and indoor unit type. Read them by outdoor dry bulb and indoor wet/dry bulb conditions at a stated airflow.

  1. Find the table for the capacity (9K, 12K, 18K, 24K, 30K or 36K) and the indoor unit type (high wall, one-way cassette, 4-way cassette, AE console, ceiling and floor console, low or high static slim duct, AHU2).
  2. Note the airflow (CFM) printed at the start of the block.
  3. Find the outdoor dry bulb (DB) row, from -22°F (-30°C) up to 122°F (50°C).
  4. Find the column for the indoor wet bulb (WB) and indoor dry bulb (DB) pair.
  5. Read TC, S/T and PI from the same row and column.
  6. Check that the reading is for the correct airflow block, because each block repeats the same conditions for another CFM value.

How to read the D5CSRA cooling performance tables

Viessmann · D5CSRA cooling performance tables, Tables 14 to 42 (pages 16 to 24 contain Tables 14 to 16 and the start of Table 15 and 16 blocks)

Each cooling table is split into blocks. Every block is headed by an airflow in CFM. Inside a block, rows are outdoor dry-bulb temperatures and columns are indoor wet-bulb and dry-bulb temperatures. Each cell holds three values labelled TC, S/T and PI. The pages do not define these three abbreviations.

  1. Pick the cooling table that matches the indoor unit type and nominal size (for example Table 16, 12K cooling, high wall).
  2. Find the airflow block that matches the CFM you are using.
  3. Go to the outdoor dry-bulb row for the outdoor temperature you are working at.
  4. Read across to the indoor wet-bulb group, then to the indoor dry-bulb column for the room conditions.
  5. Read the TC, S/T and PI values from that cell. Check the table footnotes for the definition of each value.

Indoor unit clearances

Viessmann · DLFSHC indoor units, sizes 06K-36K

Keep the top clearance at 5.9 in (15 cm) minimum for proper return airflow. The top clearance may be reduced to 2 in (50 mm) only if the left and right clearances are met. Reduced top clearance can lower unit performance. Keep 4.75 in (12 cm) minimum at the sides, and keep 6 ft (1.8 m) clearance as marked in the clearance figure.

  1. Allow space for airflow and service.
  2. Check top clearance: 5.9 in (15 cm) minimum.
  3. If top clearance is reduced to 2 in (50 mm), confirm the left and right clearances are met.
  4. Check side clearance: 4.75 in (12 cm) minimum.

Indoor unit does not respond to the remote

Viessmann · DLCSRB indoor high wall units

Use the remote controller to check the indoor unit first. The manual says a non-responding unit points to the indoor PCB, while a responding unit with a display fault points to the display board.

  1. Operate the unit with the remote controller.
  2. If the unit does not respond to the remote, replace the indoor PCB.
  3. If the unit responds to the remote but the display shows a fault, replace the display board.

Indoor unit filter access

Viessmann · DLFSCBH and DLFLCBH

The grille hinges open for access to the cleanable filters, indoor fan motor and control box. The filter track is at the top of the unit and factory supplied filters are cleanable.

  1. Open the hinged grille.
  2. Remove the cleanable filters from the filter track at the top of the unit and clean them.

Indoor-to-outdoor wiring rules

Viessmann · All sizes

Connections between indoor and outdoor units are polarity sensitive. Wrong termination causes a fault code.

  1. Do not use thermostat wire for any connection between indoor and outdoor units.
  2. Connect the indoor and outdoor units exactly as the connection diagram shows.
  3. Check polarity on every connection, since improper termination gives a fault code.

Installation prerequisites: disconnect and leak test gas

Viessmann · DLFSHC installation and service

Lock out the main electrical disconnect before installing, modifying or servicing. Never use air or oxygen-containing gases for leak testing or running refrigerant compressors.

  1. Switch off the main electrical disconnect and lock and tag it before work starts.
  2. Do not use air or oxygen-containing gas for leak testing.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.