Commissioning: Mini-Split tips (part 2 of 3)
Short, practical technician tips on commissioning for mini-split. Check each one against the manual for your exact model before acting.
Refrigerant line length and burial limits
Carrier · D5FSFAH 9K to 16K, R-454B system
Line sets are sized on runs up to 25 ft. Longer runs need extra charge within the allowable length from the product data.
- Keep the minimum line length between indoor and outdoor units at 10 ft (3 m).
- Do not bury more than 36 in (914 mm) of line. If any section is buried, give it a 6 in (152 mm) vertical rise to the service valves.
- Insulate both lines separately with at least 1/2 in (12.7 mm) insulation; closed-cell is recommended on long runs.
- Isolate the tubing from the building structure so vibration and noise do not transfer.
- For runs over 25 ft, add refrigerant up to the allowable length in the product data.
Remote control range and timer distance
Carrier · Wireless remote RG10F8(2)/BGEFU1
The remote works up to 26 ft (8 m) with no obstructions. When the timer is used, keep the remote within 26 ft (8 m) of the indoor unit. The remote is shared across other indoor units.
- Point the remote at the right side of the unit when sending commands.
- Listen for the beep to confirm the unit received the command.
Single zone performance check record
Carrier · Single zone systems
For 1:1 single zone systems, record operating data after the unit has run.
- Adjust the set-point to create an operational call for the test.
- Let the system run for at least 10 minutes.
- Record T1, T2, T3, T4, Tb, Tp, Th and LA/Lr with the remote controller Point Check function.
- Record any indoor or outdoor error codes and wall controller and 24V interface notes.
Start-up checklist items to record
Carrier · Ductless start-up checklist
Items to write on the start-up checklist before leaving the job.
- Record wire size and type, and confirm no splices or wire nuts between outdoor and indoor units.
- Verify the wiring from the outdoor port to the correct indoor unit.
- Record liquid line size, length and additional charge. Record the final charge.
- Confirm the line set matches the evaporator connection diameter.
- Record whether any error codes were present at start-up.
- Record the indoor and outdoor error codes, if any, on the checklist.
Timer function is relative, not clock time
Carrier · D5FCFA
The 24-hour timer does not change the running mode. If the unit is off when a timer-off is set, it stays off until the timer on time is reached.
- Set Timer On, Timer Off, Timer On/Off or Timer Off/On on the remote.
- Confirm the unit's current mode is unchanged after the timer is set.
Wall hole slope for drainage
Carrier · D5FSHA sizes 6K to 36K
The wall hole must drain toward the outside so condensate does not run back into the room.
- Drill the wall hole with a 2.5 in (65 mm) or 3.54 in (90 mm) core drill.
- Drill at a slight downward angle so the outdoor end is about 0.2-0.275 in (5-7 mm) lower than the indoor end.
- Place the protective wall cuff in the hole.
Buried refrigerant line limits
Viessmann · DLCURA refrigerant lines
Do not bury more than 36 in (914 mm) of refrigerant pipe. If any section is buried, the pipe must rise at least 6 in (152 mm) to the outdoor unit valve connections. Longer buried runs let refrigerant migrate to the cold section during shutdown and can cause slugging and compressor damage at start-up.
Buried refrigerant pipe limits
Viessmann · Refrigerant piping routed underground
Burying refrigerant pipe deeper or longer than allowed can let refrigerant migrate into the cold buried section during shutdown, causing slugging and possible compressor damage at start-up.
- Do not bury more than 36 in. (914 mm) of refrigerant pipe.
- If any pipe is buried, provide a 6 in. (152 mm) vertical rise to the outdoor unit valve connections.
Check refrigerant charge when the line run is longer than standard
Viessmann · D5CSRA outdoor units
Each size has a factory charge and a standard piping length of 24.6 ft (7.5 m). Longer runs need extra refrigerant, and total piping is limited by size, up to 213.25 ft (65 m) on the 36K.
- Confirm the total line length is within the limit for the size.
- For each foot of line beyond 24.6 ft (7.5 m), add refrigerant at the rate shown for the size: 0.16 oz/ft (15 g/m) for 9K to 18K, or 0.32 oz/ft (30 g/m) for 24K to 36K.
- Check the height difference between indoor and outdoor units against the size limit.
Customer handover items
Viessmann · All sizes
Walk the customer through the owner's functions with the owner's manual, then leave both manuals with them.
- Show how to switch on and off, select COOL, HEAT and other modes, set temperature and timer, and use the display panel.
- Show how to remove and clean the air filter.
- Show how to set the air deflection louver.
- Explain care and maintenance.
- Leave the owner's manual and installation instructions with the customer.
Deep vacuum target before charging
Viessmann · Refrigerant tubing and indoor coil
Deep vacuum to 500 microns is the preferred method for removing air and water from the tubing and indoor coil.
- Use a vacuum gauge that reads accurately at 500 microns.
- Break vacuums only with dry nitrogen.
Field wiring rules
Viessmann · DLCURA field wiring
Field wiring must be finished by a qualified electrician. Ground the unit per local code and install a current leakage protection device.
- Connect power only to terminals L1 or L2. Power on any other terminal damages the control board.
- Keep control wiring in a separate conduit from power wiring, at least 12 in (300 mm) apart. Metallic conduit or shielded cable is recommended.
- Match wire colours and terminal numbers to the indoor unit.
- Tighten all connections firmly. Loose wiring can overheat terminals.
- Keep wires clear of refrigerant tubing, the compressor and moving parts.
- Provide a disconnect within sight of and readily accessible from the unit.
Final checks before handover
Viessmann · DLFSCBH / DLFLCBH, sizes 24-48
Check the indoor and outdoor unit functions and the drain before handing the system over to the customer.
- Confirm all remote control buttons work.
- Confirm the display panel lights work.
- Confirm the air deflection louver moves.
- Confirm the drain works.
- Check for unusual noise or vibration at the outdoor unit.
- Explain operation, filter cleaning, louver setting and maintenance to the customer, and leave the owner's manual and this manual with them.
Final tubing check and do not use compressor for vacuum
Viessmann · Refrigerant tubing, all DLFSHC sizes
Make sure factory tubing has not shifted in shipping and is not rubbing on other tubes or sheet metal. Check the wire ties on the feeder tubes. Never use the system compressor as a vacuum pump.
- Check indoor and outdoor factory tubing for shift from shipping.
- Check that tubes do not touch each other or sheet metal.
- Check that the wire ties on the feeder tubes are secure and tight.
- Do not run the compressor to pull vacuum.
Fit compressor crankcase heater clamps
Viessmann · D5CSRA outdoor units
The crankcase heater is standard on all sizes. Its clamps must be placed around the compressor oil sump.
- Confirm the crankcase heater is fitted on the compressor.
- Place the heater clamps around the compressor oil sump.
Humidity sensor is inactive on some system types
Viessmann · DRY mode humidity control
The humidity setting is not active when the floor console is matched with a multi-zone outdoor unit or a wired controller is used.
- Check the system type before relying on the remote humidity setting.
- Use a wired controller or multi-zone match only with the understanding that the humidity sensor is disabled.
Indoor to outdoor wiring requirements
Viessmann · DLFSCBH and DLFLCBH 24K, 36K, 48K
Power and communication run as four conductors. Polarity matters, and BX cable is not recommended.
- Size wire per NEC or CEC and local codes, using the MCA and MOCP values from the electrical data table.
- Use 14/3 stranded wire with ground, 600 V rated, between outdoor and indoor units.
- Two conductors carry line voltage, one is communication (S), and one is ground.
- Keep the wiring polarity correct between the indoor and outdoor units.
- In high EMF areas with communication problems, use 14/2 stranded shielded wire for L2 and S, and land the shield to ground at the outdoor unit only.
- Make every connection tight and keep wires clear of refrigerant tubing, the compressor and moving parts.
- Provide a disconnect within sight of and readily accessible from the air conditioner.
Indoor unit power supply
Viessmann · DLFSCBH and DLFLCBH, sizes 24K, 36K, 48K
The indoor fan motor runs on 208-230 V. Power is supplied from the outdoor unit, so no separate supply is needed at the indoor unit.
Insulate both refrigerant lines separately
Viessmann · Refrigerant line install, all DLFSHC sizes
Both refrigerant lines must be insulated on their own. Use the outdoor unit installation instructions for other allowed piping lengths and refrigerant details.
- Insulate the liquid line and the suction line separately.
- Check the outdoor unit installation instructions for allowed piping lengths and refrigerant data.
Keep wall clearance and snow height for the outdoor unit
Viessmann · D5CSRA outdoor units
Use the wall-height clearance table before mounting. The unit cannot be installed where the wall behind it is taller than the unit. Mount the outdoor unit at least 2 in (50 mm) above the deepest expected snow.
- Measure the wall height behind the unit and compare it with the unit height.
- Keep at least 9.8 in (25 cm) to the wall when the wall is half the unit height or less.
- Keep at least 11.8 in (30 cm) when the wall is between half the unit height and the full unit height.
- Raise the unit at least 2 in (50 mm) above the expected snow depth.
Leak testing and lockout
Viessmann · All installation and service work
Never use air or gas containing oxygen for leak testing or for running refrigerant compressors. Mixtures can explode. Before any installation or service, the main disconnect must be off and locked out and tagged.
- Use dry nitrogen or other non-oxygen gas for leak testing.
- Turn off the main electrical disconnect, lock it out and tag it before working.
- Check for more than one disconnect switch.
Outdoor unit mounting, leveling and clearance
Viessmann · Outdoor unit, 36K-58K
Mount the outdoor unit level in all planes, in a spot that can carry its weight, is convenient to install, and is not exposed to strong wind. Keep the minimum clearances from the manual's clearance figure so air can flow freely and service access is kept.
- Check the unit is level in all planes before final connection.
- Confirm the mounting spot can bear the weight of the outdoor unit.
- Keep the minimum clearance shown on the clearance figure (Fig. 6, page 14) for airflow and service.
- Make sure air inlets and outlets are not restricted.
- Do not install in areas with special environmental conditions without contacting the sales representative.
Outdoor unit power supply
Viessmann · DLCURA outdoor units, 1.5T to 5T
The DLCURA outdoor unit runs on single-phase 60 Hz power at 208/230 V for the listed sizes. It has one point of electrical connection. Wiring must follow the NEC and local codes. High-voltage and low-voltage terminal blocks are provided.
- Confirm the supply is 208/230 V, single-phase, 60 Hz before connecting.
- Make one single point power connection to the unit.
- Run high-voltage and low-voltage wiring per NEC and local code, using the separate terminal blocks.
Panel installation sequence
Viessmann · Cassette indoor unit
Install the panel only after piping and wiring work is complete.
- Finish refrigerant piping and wiring first.
- Install the panel afterwards.
Power and communication wiring layout
Viessmann · 36K-58K ductless systems
Main power goes to the outdoor unit only. The indoor unit receives power through the 3-wire link from the outdoor unit. Indoor unit does not need its own disconnect on that link, but a 3-pole disconnect can be added for extra protection.
- Feed the main power to the outdoor unit.
- Run the 3-wire power link from outdoor to indoor unit.
- Run the separate shielded communication wire from outdoor to indoor unit.
- Provide a separate supply for any auxiliary electric heater.
Power off before dip switch changes
Viessmann · DLCURA outdoor and compatible indoor units
Dip switch settings are only read at power-up, so switch power off before changing any of them.
- Turn power OFF at the outdoor unit.
- Set the dip switches (S1 on the outdoor unit, S4 on the indoor unit).
- Restore power.
Refrigerant line connection options
Viessmann · DLFSCBH and DLFLCBH
Refrigerant lines can be oriented to connect from the left, right or back of the unit. Both refrigerant lines must be insulated.
- Choose the connection side (left, right or back) for the refrigerant lines.
- Insulate both refrigerant lines.
Refrigerant line length and insulation
Viessmann · Indoor to outdoor refrigerant piping
The minimum refrigerant line length between indoor and outdoor units is 10 ft (3 m). Both refrigerant lines must be insulated separately.
- Keep the line run at least 10 ft (3 m).
- Insulate the gas and liquid lines separately.
Refrigerant line rules, standard and long line
Viessmann · 36K-58K ductless systems
The outdoor unit ships with a full R410A charge. Line sizing and capacities are based on 25 ft (7.6 m) runs. Long-line runs keep the same line size but need extra charge.
- Check the line set is insulated on both lines with at least 1/2 in (12.7 mm) closed-cell insulation.
- Do not bury lines deeper than 36 in (914 mm). Provide at least a 6 in (152 mm) vertical rise to the service valves to prevent refrigerant migration.
- Do not bury the lines otherwise; isolate the tubing from the building structure so vibration and noise do not transfer.
- For long-line applications, keep the same line size and add refrigerant per the Additional Charge requirement in Table 3, page 5.
Relocate the IR receiver when using a wireless remote
Viessmann · Wireless remote control installations
The factory IR receiver sits inside the control box. It must be moved within line of sight of the remote location. An authorized technician should do this.
- Use the 6 ft cable supplied with the kit.
- Route the IR receiver to a location in line of sight of where the remote will be used.
- Have an authorized technician carry out the work.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.