Viessmann Mini-Split: Refrigerant line set-up and charge
Refrigerant line set-up and charge on a Viessmann mini-split: Rules for installing the line set between the outdoor and indoor unit.
Applies to: DLCURA outdoor units with ductless indoor unit
How to fix refrigerant line set-up and charge: step by step
- Use the factory R410A charge. Line sizing and capacity are based on runs up to 25 ft (7.6 m).
- For runs longer than 25 ft, add 0.69 oz per ft (65 g per m) of extra refrigerant charge.
- Do not bury lines deeper than 36 in (914 mm).
- Give the service valves a vertical rise of at least 6 in (152 mm) to stop refrigerant migration.
- Insulate the suction line with at least 3/8 in (10 mm) wall thermal insulation.
- Isolate the tubing from the building structure so vibration and noise do not carry into the structure.
- Flow nitrogen while brazing the line set or line set adapters.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Models
36AAK48AAK58AAK80ES(N,L)80ESUDLCURAH18AAKDLCURAH18ABKDLCURAH24AAKDLCURAH24ABKDLCURAH30AAKDLCURAH30ABKDLCURAH36AAKDLCURAH36ABKDLCURAH48AAKDLCURAH48ABKDLCURAH60AAKDLCURAH60ABKFEM4FVM4X48***LFVM4X60***LFXM4X48**ALFXM4X60**AL
Source: DLCURA technical data manual, p. 82. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.