Viessmann Mini-Split: PCB Board 8 removal: IPM module board and 24V board
PCB Board 8 removal: IPM module board and 24V board on a Viessmann mini-split: Removes the IPM module board and the 24V board. Wires to the DC fan motors, compressor and main control board are involved.
Applies to: PCB Board 8 in the outdoor unit
How to fix pcb board 8 removal: ipm module board and 24v board: step by step
- Remove two screws to disconnect the power supply wires.
- Remove three screws to disconnect the compressor wires.
- Remove three screws and take off the radiator.
- Disconnect the wires between the IPM module board and the main control board.
- Remove the four screws, release the four hooks and remove the IPM module board.
- Remove one screw, disconnect the wires and remove the 24V board.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Models
36AAK48AAK58AAK80ES(N,L)80ESUDLCURAH18AAKDLCURAH18ABKDLCURAH24AAKDLCURAH24ABKDLCURAH30AAKDLCURAH30ABKDLCURAH36AAKDLCURAH36ABKDLCURAH48AAKDLCURAH48ABKDLCURAH60AAKDLCURAH60ABKFEM4FVM4X48***LFVM4X60***LFXM4X48**ALFXM4X60**AL
Source: DLCURA service manual, p. 71 of 84. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.