Viessmann Mini-Split: Field wiring rules
Field wiring rules on a Viessmann mini-split: Field wiring must be finished by a qualified electrician. Ground the unit per local code and install a current leakage protection device.
Applies to: DLCURA field wiring
How to fix field wiring rules: step by step
- Connect power only to terminals L1 or L2. Power on any other terminal damages the control board.
- Keep control wiring in a separate conduit from power wiring, at least 12 in (300 mm) apart. Metallic conduit or shielded cable is recommended.
- Match wire colours and terminal numbers to the indoor unit.
- Tighten all connections firmly. Loose wiring can overheat terminals.
- Keep wires clear of refrigerant tubing, the compressor and moving parts.
- Provide a disconnect within sight of and readily accessible from the unit.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Models
36AAK48AAK58AAK80ES(N,L)80ESUDLCURAH18AAKDLCURAH18ABKDLCURAH24AAKDLCURAH24ABKDLCURAH30AAKDLCURAH30ABKDLCURAH36AAKDLCURAH36ABKDLCURAH48AAKDLCURAH48ABKDLCURAH60AAKDLCURAH60ABKFEM4FVM4X48***LFVM4X60***LFXM4X48**ALFXM4X60**AL
More commissioning tips for mini-split
Source: Viessmann DLCURA Service Manual, p. 3-4. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.