Viessmann Mini-Split: Field wiring installation checks (indoor to outdoor unit)
Field wiring installation checks (indoor to outdoor unit) on a Viessmann mini-split: Checks to make before energising the indoor and outdoor units. Power and communication run between the two units in one cable set.
Applies to: DLFSCBH and DLFLCBH, sizes 24K, 36K, 48K
Common causes of field wiring installation checks (indoor to outdoor unit)
- Loose terminals can overheat and cause unit malfunction or a fire hazard.
- Communication problems can come from electromagnetic interference in high EMF areas.
How to fix field wiring installation checks (indoor to outdoor unit): step by step
- Size all wires per NEC or CEC and local codes, using the MCA and MOCP values from the electrical data table.
- Use field supplied 14/3 stranded wire with ground, 600 V rated, for the power and communication run.
- Keep the four conductors correct: two line voltage, one communication (S) and one ground.
- Keep polarity correct on the indoor to outdoor wiring, as it is polarity sensitive.
- Do not use BX cable.
- In a high EMF area with communication problems, use 14/2 stranded shielded wire for L2 and S and ground the shield at the outdoor unit only.
- Tighten every wire connection.
- Route no wire against refrigerant tubing, the compressor or any moving part.
- Provide a disconnect within sight of, and readily accessible from, the unit.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Source: Vitocal IND-C technical data manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.