Viessmann Mini-Split: Buried refrigerant line limits
Buried refrigerant line limits on a Viessmann mini-split: Do not bury more than 36 in (914 mm) of refrigerant pipe. If any section is buried, the pipe must rise at least 6 in (152 mm) to the outdoor unit valve connections. Longer buried runs let refrigerant migrate to the cold section during shutdown and can cause slugging and compressor damage at start-up.
Applies to: DLCURA refrigerant lines
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Models
36AAK48AAK58AAK80ES(N,L)80ESUDLCURAH18AAKDLCURAH18ABKDLCURAH24AAKDLCURAH24ABKDLCURAH30AAKDLCURAH30ABKDLCURAH36AAKDLCURAH36ABKDLCURAH48AAKDLCURAH48ABKDLCURAH60AAKDLCURAH60ABKFEM4FVM4X48***LFVM4X60***LFXM4X48**ALFXM4X60**AL
More commissioning tips for mini-split
Source: Viessmann DLCURA Service Manual, p. 1. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.