Updated · by Aurora Star Tech Inc.

Force cooling for testing on a Daikin mini-split: Run the unit without waiting on thermostat.

Homeowner with a ductless mini-split problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

Common causes of force cooling for testing

  • Only allowed when the outdoor unit has no error, is not in 3 minute standby and is off

How to fix force cooling for testing: step by step

  1. Hold the indoor ON/OFF switch 5 seconds (stops after about 15 minutes).
  2. Or from the remote: Temp up, Temp down and Mode together, pick T, press Mode, pick cooling, press On/Off (stops after about 30 minutes).
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Mini-Split codes

Models

FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9

Source: Daikin FTX-W service manual SiUS042228E, Forced cooling operation, p.124. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.