Updated · by Aurora Star Tech Inc.

Check power module and diode bridge for shorts on a Daikin mini-split: Resistance checks on a de-energized unit.

Homeowner with a ductless mini-split problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

How to fix check power module and diode bridge for shorts: step by step

  1. Wait until the bus voltage is near 0 V. FU2 to DC- must read 50 V or less before touching anything.
  2. Diode bridge (DB1): infinite or under 1 kohm between pins means a short.
  3. Power module: unplug the compressor harness and measure U, V, W against the (+) and (-) terminals. Good is several kohm to several Mohm; 0 ohm or infinite is bad.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Mini-Split codes

Models

FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9

Source: Daikin FTX-W service manual SiUS042228E, Main circuit short check 5.12 to 5.14, p.119. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.