Daikin Mini-Split: Check outdoor fan motor
Check outdoor fan motor on a Daikin mini-split: Voltage test at connector S70.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
How to fix check outdoor fan motor: step by step
- Power off. Unplug S70.
- Check about 320 VDC on pins 4-7, 15 VDC on 4-3, 0 to 6.5 VDC on 4-2.
- Reconnect with power off. Turn the fan by hand one turn and look for 4 pulses (0 to 15 VDC) on pins 4-1.
- Bad voltage at step 2: replace outdoor PCB. Pulses missing: replace the fan motor.
If the unit shows an error code, look it up: Daikin Mini-Split codes
Models
FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9
Source: Daikin FTX-W service manual SiUS042228E, Outdoor fan motor check 5.8, p.117. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.