Carrier Mini-Split: Temperature sensor open or short circuit check (EH60, EH61, EH62, EH65, EH66, EC52, EC53, EC54, EC56)
Temperature sensor open or short circuit check (EH60, EH61, EH62, EH65, EH66, EC52, EC53, EC54, EC56) on a Carrier mini-split: A sensor is faulty when the sampled voltage is below 0.06 V or above 4.94 V.
Applies to: D5FSOAH sensors
Common causes of temperature sensor open or short circuit check (eh60, eh61, eh62, eh65, eh66, ec52, ec53, ec54, ec56)
- Open or shorted sensor
- Loose or damaged sensor wiring
- Faulty PCB input
How to fix temperature sensor open or short circuit check (eh60, eh61, eh62, eh65, eh66, ec52, ec53, ec54, ec56): step by step
- Disconnect the temperature sensor from the PCB.
- Measure the sensor resistance with a multimeter.
- Compare the reading with the sensor resistance table in the appendix (p. 64).
- Check the connection between the sensor and the PCB. Fix wiring if needed.
- If the reading is outside the acceptable range, replace the sensor.
- If the sensor and wiring are good, replace the indoor PCB (EH codes) or outdoor PCB (EC codes).
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
D5FSOAH06XAKD5FSOAH12XAKD5FSOAH18XAK
Source: D5FSOAH service manual, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.