Carrier Mini-Split: System evacuation and charging
System evacuation and charging on a Carrier mini-split: Evacuate tubing and indoor coil with a 500 micron deep vacuum, or use the triple evacuation method if the pump cannot reach 500 microns and the system holds no liquid water. Always break vacuum with dry nitrogen. Factory charge in the outdoor unit covers up to 25 ft (8 m) of line; longer lines need added refrigerant up to the allowable length.
Applies to: D5FCFAH
How to fix system evacuation and charging: step by step
- Tighten the flare nuts fully before connecting.
- Connect the manifold gauge charge hose to a charge port on the low side service valve.
- Connect the charge hose to the vacuum pump, fully open the low side of the manifold, and start the pump.
- Evacuate by deep vacuum (500 micron) or triple evacuation.
- For triple evacuation: pull down to 28 inHg, run the pump 15 more minutes, close valves, and break vacuum with dry nitrogen to 2 psig.
- Let the system stand for 1 hour, then repeat the nitrogen and evacuation cycle as shown in the service figure.
- When evacuation is complete, close the manifold low side and stop the pump.
- For lines over 25 ft (8 m), add refrigerant up to the allowable length.
- Disconnect the charge hose, fully open service valves B and A, and tighten the valve caps.
- Never use the compressor as a vacuum pump.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
D5FCFAH18XAKD5FCFAH24XAKD5FCFAH36XAKD5FCFAH48XAKD5FCFAH58XAKD5FCFH18XAKD5FCFH24XAKD5FCFH36XAKD5FCFH48XAKD5FCFH58XAKD5SCHA
Source: D5FCFAH service manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.