Updated · by Aurora Star Tech Inc.

Start-up leak check and evacuation on a Carrier mini-split: Piping checks to complete during start-up of the ductless system.

Homeowner with a ductless mini-split problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Refrigerant piping

How to fix start-up leak check and evacuation: step by step

  1. Hold the system at 500 psig (maximum 550 psi) for at least 30 minutes using dry nitrogen. Never use air or oxygen-containing gases.
  2. Use the Triple Evacuation Method or the Deep Vacuum Method as outlined in the installation manual.
  3. Confirm the system holds 500 microns for 1 hour after deep vacuum.
  4. Confirm the line set diameter matches the evaporator connections.
  5. For conventional fan coils, confirm the line set matches the outdoor unit size.
  6. Measure the liquid line length, calculate the additional charge, and record the final charge amount.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Mini-Split codes

Source: Carrier D5FSHA installation manual, p. 28. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.