Carrier Mini-Split: Refrigerant recovery, purge and evacuation before opening circuit
Refrigerant recovery, purge and evacuation before opening circuit on a Carrier mini-split: Required sequence for flammable refrigerant work on the circuit.
Applies to: Flammable refrigerant service
How to fix refrigerant recovery, purge and evacuation before opening circuit: step by step
- Recover refrigerant safely into correct recovery cylinders per local and national rules.
- Evacuate the system.
- Purge the circuit with oxygen-free nitrogen.
- Evacuate again.
- Flush or purge with nitrogen when using flame to open the circuit, then open the circuit.
- For purging, break vacuum with oxygen-free nitrogen, fill to working pressure, vent, then pull vacuum; repeat until no refrigerant remains.
- Vent to atmospheric pressure before work. Keep the vacuum pump outlet away from ignition sources.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Source: Carrier D5FSHA installation manual, p. 6. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.