Carrier Mini-Split: Refrigerant line length and burial limits
Refrigerant line length and burial limits on a Carrier mini-split: Line sets are sized on runs up to 25 ft. Longer runs need extra charge within the allowable length from the product data.
Applies to: D5FSFAH 9K to 16K, R-454B system
How to fix refrigerant line length and burial limits: step by step
- Keep the minimum line length between indoor and outdoor units at 10 ft (3 m).
- Do not bury more than 36 in (914 mm) of line. If any section is buried, give it a 6 in (152 mm) vertical rise to the service valves.
- Insulate both lines separately with at least 1/2 in (12.7 mm) insulation; closed-cell is recommended on long runs.
- Isolate the tubing from the building structure so vibration and noise do not transfer.
- For runs over 25 ft, add refrigerant up to the allowable length in the product data.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
D5FSFAH09XAKD5FSFAH12XAKD5FSFAH16XAK
More commissioning tips for mini-split
Source: D5FSFAH service manual, p. 12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.