Updated · by Aurora Star Tech Inc.

Refrigerant leak sensor response (indoor leakage sensor) on a Carrier mini-split: On detection of a leak the outdoor unit shuts off, indoor fan runs turbo, louvers fully open, and an audible alarm sounds. In single-zone systems the alarm resets after 2 minutes below LFL and the code clears after 5 minutes. Power cycling the outdoor unit for 5 minutes resets alarm and code. In multi-zone systems the emergency shutoff valve closes, all EEVs close, and the valve reopens automatically after 2.5 hours once the leak is below LFL.

Homeowner with a ductless mini-split problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: D5FCFAH

Common causes of refrigerant leak sensor response (indoor leakage sensor)

  • Refrigerant leak detected at indoor unit
  • Leak sensor out of range

How to fix refrigerant leak sensor response (indoor leakage sensor): step by step

  1. Identify the indoor unit showing EH C1 or EH C2.
  2. Locate and repair the refrigerant leak before restarting.
  3. Single zone: after the leak is gone, wait for the clear time or power cycle the outdoor unit for 5 minutes.
  4. Multi-zone: the shutoff valve time-lock can be bypassed by holding the check button in the MZU for 10 seconds, only when no leak is detected. Power cycling the MZU does not reset the time-lock.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Mini-Split codes

Models

D5FCFAH18XAKD5FCFAH24XAKD5FCFAH36XAKD5FCFAH48XAKD5FCFAH58XAKD5FCFH18XAKD5FCFH24XAKD5FCFH36XAKD5FCFH48XAKD5FCFH58XAKD5SCHA

Source: D5FCFAH service manual, p. 20. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency HVAC Service

647-657-2977