Carrier Mini-Split: R-454B (A2L flammable refrigerant) field piping, leak test and charging requirements

Updated · by Aurora Star Tech Inc.

R-454B (A2L flammable refrigerant) field piping, leak test and charging requirements on a Carrier mini-split: Requirements for field-made refrigerant work on this A2L flammable refrigerant system. Only trained and certified service personnel should work on the refrigerant circuit.

Homeowner with a ductless mini-split problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Field refrigerant piping, joints, evacuation and charging

How to fix r-454b (a2l flammable refrigerant) field piping, leak test and charging requirements: step by step

  1. Only use technicians with a current, valid refrigerant handling certificate.
  2. Keep field piping as short as practical and protect it from physical damage.
  3. Pressure test the field piping with inert gas, then vacuum test before charging.
  4. Hold the test pressure for at least 1 hour with no pressure drop on the gauge. Gauge resolution must not exceed 5% of test pressure.
  5. During evacuation, the pressure must not rise above 1500 microns within 10 minutes after isolating the pump. The vacuum target is the lesser of 500 microns or the local code value.
  6. Tightness test field-made indoor joints at at least 125% of maximum allowable pressure with a detector sensitivity of 1/8 oz (5 g)/year. No leak allowed.
  7. Do not use open flames or halide torches to search for leaks. Use a leak detector suitable for flammable refrigerants, or a bubble or fluorescent leak detection fluid.
  8. Purge the system with oxygen-free nitrogen. Do not use compressed air or oxygen.
  9. Charge by the liquid method. Do not overfill. Pressure test with OFN before recharging.
  10. Label the system as containing flammable refrigerant after charging is complete.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Mini-Split codes

Source: D5FSOAH Owner's Manual, pp. 2-5. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.