Carrier Mini-Split: Leak detection on flammable refrigerant systems
Leak detection on flammable refrigerant systems on a Carrier mini-split: Do not use a naked flame to find leaks. Electronic detectors may need recalibration for flammable refrigerants.
Applies to: Refrigerant leak search
How to fix leak detection on flammable refrigerant systems: step by step
- Do not use a halide torch or any detector with a naked flame.
- Use an electronic detector suited to the refrigerant and calibrated in a refrigerant-free area; set the alarm at no more than 25% of the LFL.
- Use bubble or fluorescent leak detection fluid if needed; avoid chlorine-based detergents.
- If a leak is found that needs brazing, recover the refrigerant or isolate that section with valves first.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
45MBCAQ12XA3D5FLCAH36XAKD5FLCAH48XAKD5FSCAH12XAKD5FSCAH18XAKD5FSCAH24XAK
Source: D5FSCAH / D5FLCAH service manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.