Carrier Mini-Split: Indoor units mode conflict (multi outdoor unit match)
Indoor units mode conflict (multi outdoor unit match) on a Carrier mini-split: Indoor units cannot run COOLING and HEATING at the same time; HEATING takes priority. If one indoor unit is in COOLING or FAN and another is set to HEATING, the cooling or fan unit powers off and the heating unit keeps running. If one unit is heating and another is set to COOLING or FAN, the cooling or fan unit goes to STANDBY and the heating unit does not change. Conflict matrix (Table 9): COOLING vs HEATING = conflict; COOLING vs FAN = no conflict; COOLING vs OFF = no conflict; HEATING vs FAN = conflict; HEATING vs OFF = no conflict; FAN vs OFF = no conflict; all other pairs = no conflict.
Applies to: D5FSFAH indoor units connected to a multi outdoor unit
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
Source: Carrier D5FSFAH service manual, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.