Carrier Mini-Split: Fan speed out of control protection
Fan speed out of control protection on a Carrier mini-split: Indoor fan below 300 RPM for 50 seconds shuts the fan off and it restarts 30 seconds later. After three restarts the unit stops and the LED shows the failure. Outdoor fan below 100 RPM or above 1500 RPM for 60 seconds stops the unit, the LED shows the failure, and the fault clears 30 seconds later.
Applies to: D5FCFAH
Common causes of fan speed out of control protection
- Indoor fan motor or speed feedback problem
- Outdoor fan motor or speed feedback problem
How to fix fan speed out of control protection: step by step
- Check the indoor fan motor and its speed signal when the indoor fan drops below 300 RPM.
- Check the outdoor fan motor and its speed signal when the outdoor fan is below 100 RPM or above 1500 RPM.
- Confirm fan motor wiring and connectors are secure.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
D5FCFAH18XAKD5FCFAH24XAKD5FCFAH36XAKD5FCFAH48XAKD5FCFAH58XAKD5FCFH18XAKD5FCFH24XAKD5FCFH36XAKD5FCFH48XAKD5FCFH58XAKD5SCHA
Source: D5FCFAH service manual, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.